SIMATIC S7-300SIMATIC PS 307 – 6ES7307-1EA01-0AA0

SIMATIC S7-300 Regulated power supply PS307 input: 120/230 V AC, output: 24
V/5 A DC

Technical Specification

Input
type of the power supply network 1-phase AC
supply voltage at AC Automatic range selection
supply voltage 120 V/230 V
input voltage 1 at AC 85 … 132 V
input voltage 2 at AC 170 … 264 V
wide range input No
overvoltage overload capability 2.3 × Vin rated, 1.3 ms
buffering time for rated value of the output current in the event of power failure minimum 20 ms
operating condition of the mains buffering at Vin = 93/187 V
line frequency 50/60 Hz
line frequency 47 … 63 Hz
input current
● at rated input voltage 120 V 2.3 A
● at rated input voltage 230 V 1.2 A
current limitation of inrush current at 25 °C maximum 20 A
duration of inrush current limiting at 25 °C
● maximum 3 ms
I2t value maximum 1.2 A²·s
fuse protection type T 3,15 A/250 V (not accessible)
fuse protection type in the feeder Recommended miniature circuit breaker: from 6 A characteristic C
Output
voltage curve at output Controlled, isolated DC voltage
output voltage at DC rated value 24 V
output voltage
● at output 1 at DC rated value 24 V
output voltage adjustable No; –
relative overall tolerance of the voltage 3%
relative control precision of the output voltage
● on slow fluctuation of input voltage 0.1 %
● on slow fluctuation of ohm loading 0.5 %
residual ripple
● maximum 50 mV
● typical 10 mV
voltage peak
● maximum 150 mV
● typical 20 mV
display version for normal operation Green LED for 24 V OK
behavior of the output voltage when switching on No overshoot of Vout (soft start)
response delay maximum 2 s
voltage increase time of the output voltage
● typical 10 ms
output current
● rated value 5:00 AM
● rated range 0 … 5 A
supplied active power typical 120 W
short-term overload current
● on short-circuiting during the start-up typical 20 A
● at short-circuit during operation typical 20 A
duration of overloading capability for excess current
● on short-circuiting during the start-up 100 ms
● at short-circuit during operation 100 ms
bridging of equipment Yes
efficiency
efficiency in percent 87%
power loss [W]
● at rated output voltage for rated value of the output current typical 18 W
closed-loop control
relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical 0.1 %
relative control precision of the output voltage load step of resistive load 50/100/50 % typical 1%
setting time
● load step 50 to 100% typical 0.3 ms
● load step 100 to 50% typical 0.3 ms
protection and monitoring
design of the overvoltage protection Additional control loop, shutdown at < 28.8 V, automatic restart
property of the output short-circuit proof Yes
design of short-circuit protection Electronic shutdown, automatic restart
response value current limitation 5.5 … 6.5 A
enduring short circuit current RMS value
● maximum 7 A
safety
galvanic isolation between input and output Yes
galvanic isolation Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178
operating resource protection class Class I
leakage current
● maximum 3.5 mA
● typical 0.5 mA
protection class IP IP20
EMC
standard
● for emitted interference EN 55022 Class B
● for mains harmonics limitation EN 61000-3-2
● for interference immunity EN 61000-6-2
standards, specifications, approvals
certificate of suitability
● CE marking Yes
● UL approval Yes; cULus-Listed (UL 508, CSA C22.2 No. 142), File E143289
● CSA approval Yes; cULus-Listed (UL 508, CSA C22.2 No. 142), File E143289
● UKCA marking Yes
● EAC approval Yes
● NEC Class 2 No
type of certification
● BIS Yes; R-41183539
● CB-certificate Yes
MTBF at 40 °C 2 480 589 h
standards, specifications, approvals hazardous environments
certificate of suitability
● IECEx Yes; IECEx Ex nA nC IIC T3 Gc
● ATEX Yes; ATEX (EX) II 3G Ex nA nC IIC T3 Gc
● ULhazloc approval Yes
● cCSAus, Class 1, Division 2 No
● UKEX Yes
● CCC for hazardous zone according to GB standard Yes
● FM registration Yes; Class I, Div. 2, Group ABCD, T4
standards, specifications, approvals marine classification
shipbuilding approval Yes
Marine classification association
● American Bureau of Shipping Europe Ltd. (ABS) No
● French marine classification society (BV) No
● Det Norske Veritas (DNV) Yes
● Lloyds Register of Shipping (LRS) Yes
standards, specifications, approvals Environmental Product Declaration
Environmental Product Declaration Yes
global warming potential [CO2 eq]
● total 504.2 kg
● during manufacturing 11.3 kg
● during operation 492.3 kg
● after end of life 0.41 kg
ambient conditions
ambient temperature
● during operation 0 … 60; with natural convection
● during transport -40 … +85
● during storage -40 … +85
environmental category according to IEC 60721 Climate class 3K3, 5 … 95% no condensation
connection method
type of electrical connection screw terminal
● at input L, N, PE: 1 screw terminal each for 0.5 … 2.5 mm² single-core/finely stranded
● at output L+, M: 3 screw terminals each for 0.5 … 2.5 mm²
● for auxiliary contacts
mechanical data
width × height × depth of the enclosure 60 × 125 × 120 mm
installation width × mounting height 60 mm × 205 mm
required spacing
● top 40 mm
● bottom 40 mm
● left 0 mm
● right 0 mm
fastening method Can be mounted onto S7 rail
● DIN-rail mounting No
● S7 rail mounting Yes
● wall mounting No
housing can be lined up Yes
net weight 0.6 kg
accessories
mechanical accessories Mounting adapter for standard mounting rail (6EP1971-1BA00)