Main Product
Overload relay – 3RB3026-1SB0 3…12 A Electronic For motor protection Size S0, Class 10E Contactor mounting Main circuit: Screw Auxiliary circuit: Screw Manual-Automatic Reset
Technial Specification
product brand name | SIRIUS |
product designation | solid-state overload relay |
product type designation | 3RB3 |
General technical data | |
size of overload relay | S0 |
size of contactor can be combined company-specific | S0 |
power loss [W] for rated value of the current at AC in hot operating state | 0.6 W |
● per pole | 0.2 W |
insulation voltage with degree of pollution 3 at AC rated value | 690 V |
surge voltage resistance rated value | 6 kV |
maximum permissible voltage for protective separation | |
● in networks with ungrounded star point between auxiliary and auxiliary circuit | 300 V |
● in networks with grounded star point between auxiliary and auxiliary circuit | 300 V |
● in networks with ungrounded star point between main and auxiliary circuit | 600 V |
● in networks with grounded star point between main and auxiliary circuit | 690 V |
shock resistance | 15g / 11 ms |
● according to IEC 60068-2-27 | 15g / 11 ms; Signaling contact 97 / 98 in position “Tripped”: 9g / 11 ms |
vibration resistance | 1-6 Hz, 15 mm; 6-500 Hz, 20 m/s²; 10 cycles |
thermal current | 12 A |
recovery time after overload trip | |
● with automatic reset typical | 3 min |
● with remote-reset | 0 min |
● with manual reset | 0 min |
reference code according to IEC 81346-2 | F |
Substance Prohibitance (Date) | 10/1/2009 |
SVHC substance name | Lead monoxide (lead oxide) – 1317-36-8 |
Weight | 0.235 Kg |
Ambient Condition | |
installation altitude at heigh above sea level maksimum | 2000 m |
ambient temperature | |
● during operation | -25 … +60 °C |
● during storage | -40 … +80 °C |
● during transport | -40 … +80 °C |
temperature compensation | -25 … +60 °C |
realtive humidity during operation | 10 … 95 % |
Main Circuit | |
number of poles for main current circuit | 3 |
adjustable current response value current of the current-dependent overload release | 3 … 12 A |
operating voltage | |
● rated value | 690 V |
● at AC-3e rated value maximum | 690 V |
operating frequency rated value | 50 … 60 Hz |
operational current rated value | 12 A |
operational current at AC-3e at 400 V rated value | 12 A |
operating power | |
● for 3-phase motors at 400 V at 50 Hz | 1.5 … 5.5 kW |
● for AC motors at 500 V at 50 Hz | 1.5 … 5.5 kW |
● for AC motors at 690 V at 50 Hz | 2.2 … 7.5 kW |
Auxiliary circuit | |
design of the auxiliary switch | integrated |
number of NC contacts for auxiliary contacts | 1 |
● note | for contactor disconnection |
number of NO contacts for auxiliary contacts | 1 |
● note | for message “tripped” |
number of CO contacts for auxiliary contacts | 0 |
operational current of auxiliary contacts at AC-15 | |
● at 24 V | 4 A |
● at 110 V | 4 A |
● at 120 V | 4 A |
● at 125 V | 4 A |
● at 230 V | 3 A |
operational current of auxiliary contacts at DC-13 | |
● at 24 V | 2 A |
● at 60 V | 0.55 A |
● at 110 V | 0.3 A |
● at 125 V | 0.3 A |
● at 220 V | 0.11 A |
Protective and monitoring functions trip class | CLASS 10E |
design of the overload release | electronic |
UL/CSA ratings | full-load current (FLA) for 3-phase AC motor |
● at 480 V rated value | 12 A |
● at 600 V rated value | 12 A |
contact rating of auxiliary contacts according to UL | B600 / R300 |
Short-circuit protection | |
design of the fuse link | |
● for short-circuit protection of the main circuit | |
— with type of coordination 1 required | gG: 63 A, RK5: 45 A |
— with type of assignment 2 required | gG: 50 A, J: 45 A |
● for short-circuit protection of the auxiliary switch required | fuse gG: 6 A |
Installation/ mounting/ dimensions | |
mounting position | any |
fastening method | Contactor mounting |
height | 87 mm |
width | 45 mm |
depth | 84 mm |
Connections/ Terminals | |
product component removable terminal for auxiliary and control circuit | Yes |
type of electrical connection | |
● for main current circuit | screw-type terminals |
● for auxiliary and control circuit | screw-type terminals |
arrangement of electrical connectors for main current circuit | Top and bottom |
type of connectable conductor cross-sections for main contacts | |
● solid | 2x (1 … 2.5 mm²), 2x (2.5 … 10 mm²) |
● stranded | 2x 10 mm² |
● solid or stranded | 1x (1 … 10 mm²), 2x (1 … 10 mm²) |
● finely stranded with core end processing | 1x (1 … 6 mm²), 2 x (1 … 6 mm²), 1x 10 mm² |
type of connectable conductor cross-sections | |
● for auxiliary contacts — solid | 1x (0.5 … 4 mm²), 2x (0.5 … 2.5 mm²) |
— solid or stranded | 1x (0,5 … 4 mm²), 2x (0,5 … 2,5 mm²) |
— finely stranded with core end processing | 1x (0.5 … 2.5 mm²), 2x (0.5 … 1.5 mm²) |
● for AWG cables for auxiliary contacts | 1x (20 … 14), 2x (20 … 14) |
tightening torque | |
● for main contacts with screw-type terminals | 2 … 2.5 N·m |
● for auxiliary contacts with screw-type terminals | 0.8 … 1.2 N·m |
design of screwdriver shaft Diameter | 5 to 6 mm |
size of the screwdriver tip | Pozidriv PZ 2 |
design of the thread of the connection screw | |
● for main contacts | M4 |
● of the auxiliary and control contacts | M3 |
Electrical Safety | |
protection class IP on the front according to IEC 60529 | IP20 |
touch protection on the front according to IEC 60529 | finger-safe, for vertical contact from the front |
Communication/ Protocol | |
type of voltage supply via input/output link master | No |
Electromagnetic compatibility | conducted interference |
● due to burst according to IEC 61000-4-4 | 2 kV (power ports), 1 kV (signal ports) corresponds to degree of severity 3 |
● due to conductor-earth surge according to IEC 61000-4-5 | 2 kV (line to earth) corresponds to degree of severity 3 |
● due to conductor-conductor surge according to IEC 61000-4-5 | 1 kV (line to line) corresponds to degree of severity 3 |
● due to high-frequency radiation according to IEC 61000- 4-6 | 10 V in frequency range 0.15 to 80 MHz, modulation 80 % AM with 1 kHz |
field-based interference according to IEC 61000-4-3 | 10 V/m |
electrostatic discharge according to IEC 61000-4-2 | 6 kV contact discharge / 8 kV air discharge |
Display | |
display version for switching status | Slide switch |
Catalog :